Thursday, 9 April 2026

AEROSOL FIRE SUPPRESSION SYSTEM

 AEROSOL FIRE SUPPRESSION SYSTEM



Compact Fast Cost-Effective Fire Protection


NFPA 2010 Based Design Overview


Slide 2 - What is Aerosol System?


Aerosol fire suppression is a condensed solid agent system that: Releases potassium-based aerosol Suppresses fire via chemical chain reaction inhibition Works without oxygen displacement or heavy cooling


Not a gas system. Not water-based.


It's a hybrid chemical suppression technology


Slide 3


How It Works


Fire detected (heat/smoke/manual)


Generator activates (electrical/thermal)


Solid compound converts to aerosol cloud


Aerosol interrupts flame radicals (H., OH)


Result: Rapid flame knockdown in seconds


Slide 4- Design Step 1: Room Volume


Formula:


Volume = L×W×H


Example:


10m x 5m x 2.5 m


Volume = 125 m³


! Common Mistake:


People ignore ceiling height variation → leads to underdesign.


Slide 5


Design Step 2: Agent Quantity


Typical Design Factor:


80-120 g/m³ (depends on manufacturer & hazard)


Assume: 100 g/m³


+ Required Aerosol:


125 x 100 = 12,500 g (12.5 kg)


! Weak Practice:


Using random "per unit coverage"

No comments: