#Transformer testing.
Ist of all you should keep in mind Tx should be Energized within one month after testing has done.
If you wait too long ,moisture, or insulation deterioration can occurs.
#Example
you tested a transformer on Ist Jun you should Energized it before Ist July.
if delay say three months may need to repeat test.
1. Turn ratio test .TTR.
check if the voltage ratio between Pri and Secondary correct.
Limite Allowed mistake 0.5 %
if input 100V output should be 10V (example)
expected 10V.
measured 10.4 ....OK
measure 11 V not okay
Deviation |10.4-10/10×100=0.4% okay.
2. Winding Resistance test .
check wire inside Transformer like checking wire is demage or loose. checking the insulation strength of insulation
■ Detect loose Connections
■Detect demage Winding.
#Example
expected Resistance 2M ohm
measured Resistance =2.0 M ohm
If Resistance =3M ohm problem possibl fault.
3. Current Diviation in Multiple Transformer
when Transformer operate together their current should be balanced.
Rule. Deviation should not exceed 0.5 test leavel or 10% parallel operations.
#example
you have two Transformer in parallel
T1= 100KV ....current 100A
T2= 100 KV.....current 108A
Difference 8% ok within 10%
if T2 =120A 20% not acceptable.
3.PI test .
measure insulation health .
formula = IR10mint/ IR 1mint .
PI value should not less then 2
●IR at 1 minute =100Mohm
●IR at 10 minute = 250 Mohm
●PI= 250/100= 2.5 okay .
4. parallel operations
two or more Transformer working together they Shere the same load like team work .
example.
instead of one big Transformer use 2 small ones together.
●why are parallel ?
more power capacity.
backup if one fail
easy maintenance.
☆condition for parallel operations
■same voltage ratio : both must give same out put voltage
T1= 11k/415
T2= 11kv/415....OK
if T=415v and T2= 400v not okay circulating current.
■Same polarity
■Same phase .order of phase must be same .
■same tap settings.
what is Tap settings.
a Tx has a tap changer like a Switch. it is used to increase or decrease out put voltage.
■why do we need
input voltage is not always constant.
#example
sometime supply 11kv
some time it drop to 10.5 kv
but we always want output 415v .
so we adjusts Tap settings.
#example
Voltage.
input voltage low 10.5 kv (low)
output become low .move tap to higher position (+Tap)
out put becomes normal
●Case 2.
Voltage high
move tap lower position(-Tap)
output becomes normal