This daily checklist is designed for the trial/commissioning phase of a 1000 MW solar plant, focusing on verifying equipment functionality, safety compliance, and power generation performance (e.g., during the 30-day trial run). 

1. Safety and Housekeeping (Daily Pre-start)

Safety Gear & Protocol: Verify all personnel are using proper PPE (Hard hats, safety shoes, arc flash protection).

Lock-out/Tag-out (LOTO): Verify LOTO is in place for any maintenance work to prevent accidental energization.

Site Security & Access: Check perimeter fencing and ensure security protocols are active.

Housekeeping: Ensure inverter rooms, substations, and cable trenches are clean and free of combustible materials. 

2. PV Field Array Inspection (Module Maintenance) 

Visual Inspection: Inspect modules for damage (cracks, breakage).

Soiling & Shading: Check for excessive dust, bird droppings, or new shading objects (vegetation growth).

Mounting Structure (MMS): Inspect for loose nuts/bolts and check for corrosion.

Cable Management: Ensure DC cables are not dangling, damaged, or resting on the ground.

Vermin/Bird Control: Remove bird nests or vermin from arrays and junction boxes. 

3. DC System & Combiner Boxes 

Combiner Box (SMB) Inspection: Verify all SMBs are sealed, water-tight, and free of moisture/corrosion.

DC Terminations: Check that all connections are tight to prevent hot spots.

Fuse Holders: Verify all string fuses are properly seated.

Polarity Check: Confirm correct polarity at the inverter input. 

4. Inverter Station (PCU)

Alarm/Warning Check: Review SCADA for active alarms, trips, or derating.

Environmental Check: Confirm cooling fans, filters, and heat sinks are operating properly.

Voltage/Current Check: Monitor DC input and AC output voltage, current, and frequency.

Energy Generation: Record daily active power and compare against expected generation. 

5. AC System, Transformers, & Switchyard

Transformer Condition: Check WTI (Winding Temperature Indicator) and OTI (Oil Temperature Indicator).

Oil Levels & Leakage: Inspect transformer conservator tank (MOG level) and check for oil leakages.

Breakers/Isolators: Verify status of AC breakers and protection relays.

Earthing System: Visually check earthing strips for continuity and proper connections.

Breather Inspection: Check the dehydration breather (Silica Gel) of the transformer. 

6. SCADA, Communication & Weather Station (WMS) 

Data Accuracy: Ensure all inverters, SMBs, and meters are online and sending data.

Sensor Cleaning: Clean irradiance sensor plates and ambient/cell temperature sensors.

Time Synchronization: Verify all devices are synchronized with the central SCADA time.

Performance Evaluation: Monitor for any underperforming zones. 

7. Performance & Reporting (Trial Period Specific)

Performance Ratio (PR): Calculate daily PR (Target >75-80% based on project standards).

Capacity Utilization Factor (CUF): Monitor daily CUF.

Energy Delivered: Log total energy delivered to the grid (kWh/MWh).

Logbook Maintenance: Ensure all faults and maintenance actions are documented in the plant logbook. 

8. Civil & Site Infrastructure

Drainage: Check for blockages in drainage channels to prevent water logging.

Roads: Ensure site roads are accessible and in good condition for vehicular movement.

Street Lights/CCTV: Verify proper operation of per

imeter lighting and surveillance cameras.