Portable Fire Extinguishers
Self-Inspection Checklist
|
Guidelines: This checklist covers regulations issued by the U.S.
Department of Labor, Occupational Safety and Health Administration (OSHA) under
29 CFR 1910.157. It applies to the placement, use, maintenance, and testing of
portable fire extinguishers. The regulations cited apply only to private
employers and their employees, unless adopted by a State agency and applied to
other groups such as public employees. Definitions of terms in bold type are
provided at the end of the checklist.
This
checklist does not address detailed regulations covering the methods used for
hydrostatic testing of fire extinguishers. Please consult 29 CFR 1910.157 for
additional information.
|
Please Circle
|
General Requirements
|
- Are
all portable fire extinguishers approved? [29 CFR 1910.157(c)(2)]
|
Y N N/A
|
- Are
portable fire extinguishers using carbon tetrachloride or chlorobromomethane
prohibited? [29 CFR 1910.157(c)(3)]
|
Y N N/A
|
- Have
all the following portable fire extinguishers been removed from service?
[29 CFR 1910.157(c)(5)]
- Soldered
or riveted shell self-generating soda acid.
- Self-generating
foam
- Gas
cartridge water
Note:
These types of fire extinguishers are operated by inverting
the extinguisher to rupture the cartridge or to initiate an uncontrollable
pressure-generating chemical reaction to expel the agent.
|
Y N N/A
|
- Are
portable fire extinguishers mounted, located, and identified so that
they are readily accessible? [29 CFR
1910.157(c)(1)]
|
Y N N/A
|
- Are
portable fire extinguishers fully charged, operable, and kept in their
designated places at all times? [29 CFR
1910.157(c)(4)]
|
Y N N/A
|
- If
fire extinguishers are enclosed in cabinets, is access to the cabinet
unobstructed and is the cabinet clearly visible? [recommended]
|
Y N N/A
|
- If
fire extinguishers are enclosed in cabinets with opaque doors, are doors
unlocked, and are the cabinet contents
indicated on the outside? [recommended]
|
Y N N/A
|
- When
fire extinguishers are enclosed in locked cabinets and doors are
equipped with approved visual identification clear glass
panels, are glass panes easily broken? Is the door capable
of being opened when the glass panel is broken? Is the
unlocking handle painted red? Is the direction the handle must
be pushed or pulled to open the door indicated? Is the door
labeled Fire equipment: in case of fire, break glass
and operate red handle? [recommended]
|
Y N
N/A
|
- When
fire extinguishers are enclosed in locked cabinets and doors are
completely glass, are doors labeled In case of
fire,
break glass? [recommended]
|
Y N N/A
|
- Are
extinguishers installed on the hangers or on the supplied brackets,
mounted in cabinets, or set on shelves unless the extinguishers
are of the wheeled type? [recommended]
|
Y N N/A
|
- Are
extinguishers installed where they are subject to physical damage
protected from impact? [recommended]
|
Y N N/A
|
Training and Education
|
- When
employees are expected to use fire extinguishers, have they been trained
in the general principles of fire extinguisher use
and the hazards involved with incipient stage fire fighting?
[29 CFR 1910.157(g)(1)]
|
Y N N/A
|
- Is
this training given at the time of initial assignment and annually
thereafter? [29 CFR 1910.157(g)(2)]
|
Y N N/A
|
Selection and Distribution
|
- Is
at least one fire extinguisher available in each laboratory, shop, or
other career-technical room, and one fire extinguisher available
for each 2,500 square feet of floor area? [recommended]
|
Y N N/A
|
- According
to the table that follows, are portable fire extinguishers selected and
distributed based on the classes (see class
definitions at end of checklist) of anticipated fires and
on the size and degree of hazard that would affect their
use? [29 CFR 1910.157(d)(1)]
First
Hazard Class
|
Maximum
Permitted Distance
to
Portable Fire Extinguisher
|
A
B
C
D
|
75 feet1
50 feet2
50-75 feet3
75 feet4
|
1 Uniformly
spaced standpipe systems or hose stations connected to a
sprinkler system installed for emergency use may be used instead of Class
A
portable
fire extinguishers.
2 Depending on
size of extinguisher and size of fire hazard, a maximum 30 feet travel
distance may be
required.
3 Use existing
Class A or Class B hazards to determine the required pattern.
4 Required where
combustible metal powders, flakes, shavings or similarly sized products
are generated
at
least once very two weeks.
|
|
Y N N/A
|
Inspection, Maintenance, and Testing
|
- Are
portable fire extinguishers inspected monthly? [29 CFR 1910.157(e)(2)]
|
Y N N/A
|
- Are
portable fire extinguishers subjected to an annual maintenance check?
[29 CFR 1910.157(e)(3)]
|
Y N N/A
|
- Does
each extinguisher have a tag or label securely attached that indicates
the month and year the inspection, maintenance,
states that recharging was performed and
identifies the person performing the service?
[recommended]
|
Y N N/A
|
- Are
records of the annual maintenance check kept and retained for at least a
year? [29 CFR 1910.157(e)(3)]
|
Y N N/A
|
- When
portable fire extinguishers are removed for service, are standby or
spare units temporarily installed of the same type
and capacity?
[29 CFR 1910.157(e)(5)]
|
Y N N/A
|
- Are
stored pressure dry chemical extinguishers that require a 12-year
hydrostatic test emptied and subjected to
applicable maintenance procedures every 6 years?
[29 CFR 1910.157(e)(4)]
Note: Dry
chemical extinguishers with non-refillable disposable containers are
exempt from this
requirement.
|
Y N N/A
|
Hydrostatic Testing
|
- Are
extinguishers hydrostatically tested at the intervals listed in the
table below?
[29 CFR 1910.157(f)(2)]
Type of Extinguishers
|
Test Interval
(years)
|
Stored
pressure water and/or
antifreeze
|
5
|
Wetting
agent
|
5
|
Aqueous
film forming agent
(AFFF)
|
5
|
Dry
chemical with stainless steel
|
5
|
Carbon
dioxide
|
5
|
Dry
chemical, stored pressure,
with mild steel, brazed brass
or aluminum shells
|
12
|
Halon
1211
|
12
|
Halon
1301
|
12
|
Dry
powder, cartridge or cylinder
operated with mild steel shells
|
12
|
|
|
Y N N/A
|
- Is
hydrostatic testing performed by trained persons with suitable testing
equipment and facilities? [29 CFR
1910.157(f)(1)]
|
Y N N/A
|
- Are
hydrostatic testing certification records maintained that show the date
of the test, the signature of the person who
performed the test, and the serial number (or other identifier)
of the fire extinguisher that was tested? [29
CFR 1910.157(f)(16)]
|
Y N N/A
|
Definitions:
Class A fire: a fire involving ordinary combustible
materials such as paper, wood, cloth, and some rubber and plastic materials.
Class B fire: a fire involving flammable or combustible
liquids, flammable gases, greases and similar materials, and some rubber and
plastic materials.
Class C fire: a fire involving energized electrical
equipment where safety requires the use of electrically nonconductive
extinguishing media.
Class D fire: a fire involving combustible metals such
as aluminum, magnesium, titanium, zirconium, sodium, lithium, and potassium.
Incipient stage fire: a fire that is in the initial or beginning
stage and can be controlled or extinguished by portable fire extinguishers,
Class II standpipe or small hose systems without the need for protective
clothing or breathing apparatus.
No comments:
Post a Comment