Sunday, 11 October 2026

Room Lux Calculation

 Room Lux Calculation



The basic lighting calculation is:


✔E= N × F × UF × MF ÷ A


Where:


✔️ E = Required illuminance (lux)


✔️N = Number of lamps/luminaires


✔️F = Lumens per lamp/luminaire


✔️UF = Utilization Factor


✔️MF = Maintenance Factor


✔️A = Room area (m²)


✅ Example


Room size = 6 m × 5 m


Area:


✔️A= 6 × 5=30m^2


Required illuminance = 300 lux


Assume:


✔️LED panel = 3,600 lm


✔️UF = 0.7


✔️MF = 0.8


✅ Required number of lights:


✔️N = E × A ÷ F × UF × MF


✔️N= 300 × 30 ÷ 3600 × 0.7 × 0.8


✔️ N = 4.46


So, select 5 LED panels of 3,600 lumens.


Practical point: Actual design should also consider mounting height, room reflectance, luminaire spacing, glare, and the required lux level for the room's use.